Servicing a Maintenance Free Battery. Start Up Project 29


6BI found that my UPS is not giving sufficient back up as expected for 20 minutes. I thought that I have to spend Rs. 800 to replace the battery. But I was not in a hurry. Want to find out the reason. After 5 minutes, the PC shutdowns. Why so? The UPS battery is not giving sufficient power (Ampere Hour) to run the load. The UPS battery is a 12 volt 7 Ah (Ampere hour) Maintenance free Sealed LeadAcid battery (SLA). That means, it is “Maintenance free” and can be used for long time without any attention. But what happens is, the cells dry out due to heat generation. This happens after 6 months to 1 year of use . It is a Lead Acid battery that requires Electrolyte in the cells. So water is necessary inside. It has 6 individual cells giving 2V each. After removing the battery from the UPS, I found that it is very easy to rejuvenate the battery through “Hydration”. The battery will become top, if the dry cells are filled with battery water. Hydrated the battery and charged. Well, now it is giving more than 15 minutes back up. Saved Rs. 800 and reduced an e-waste. You can also rejuvenate the 6V Emergency lamp battery like this. So do it yourself. It is only a 10 minutes job.

Continue reading